DG M WE 600
|
DG M WE 600 FM
|
|
Type of SPD according to EN 61643-11
|
Type 2
|
Type 2
|
|
SPD according to IEC 61643-1
|
Class II
|
Class II
|
|
Nominal a.c. voltage [UN]
|
600 V
|
600 V
|
|
Max. continuous operating a.c. voltage [UC]
|
600 V
|
600 V
|
|
Rated voltage of varistor [Umov]
|
750 V
|
750 V
|
|
Nominal discharge current (8/20 µs) [In]
|
15 kA
|
15 kA
|
|
Max. discharge current (8/20 µs) [Imax]
|
25 kA
|
25 kA
|
|
Voltage protection level [UP]
|
≤ 3 kV
|
≤ 3 kV
|
|
Voltage protection level for 5 kA [UP]
|
≤ 2.5 kV
|
≤ 2.5 kV
|
|
Response time [tA]
|
≤ 25 ns
|
≤ 25 ns
|
|
Max. mains-side overcurrent protection
|
100 A gL/gG
|
100 A gL/gG
|
|
Short circuit withstand capability for max. mains-side overcurrent protection
|
25 kArms
|
25 kArms
|
|
Temporary overvoltage (TOV) [UT]
|
900 V / 5 sec.
|
900 V / 5 sec.
|
|
Operating temperature range [TU]
|
-40°C...+80°C
|
-40°C...+80°C
|
|
Operating state/fault indication
|
green / red
|
green / red
|
|
Cross-sectional area (min.)
|
1.5 mm2 solid/flexible
|
1.5 mm2 solid/flexible
|
|
Cross-sectional area (max.)
|
35 mm2 stranded/25 mm2 flexible
|
35 mm2 stranded/25 mm2 flexible
|
|
For mounting on
|
35 mm DIN rail acc. to EN 60715
|
35 mm DIN rail acc. to EN 60715
|
|
Enclosure material
|
red thermoplastic, UL 94 V-0
|
red thermoplastic, UL 94 V-0
|
|
Degree of protection
|
IP 20
|
IP 20
|
|
Dimension
|
3 mods., DIN 4
|
3 mods., DIN 4
|
|
Approvals, Certifications
|
KEMA, UL, VdS
|
KEMA, UL, VdS
|
|
Type of remote signalling contact
|
--
|
changeover contact
|
|
Switching capacity a.c.
|
--
|
250 V/0.5 A
|
|
Switching capacity d.c.
|
--
|
250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A
|
|
Cross-sectional area for remote signalling terminals
|
--
|
max. 1.5 mm2 solid/flexible
|
|
|
1 pcs.
|
1 pcs.
|